8-60 6-00667-01 Rev B
Scalar 100
2. Use Change to select one of the following:
DEFAULT — The library reads 6 character barcode labels.
EXTENDED The library reads 5 to 13 character barcode labels.
3. Select OK.
Configuring Drive Cleaning
In most configurations, drive cleaning is controlled through the host; however, if desired, the library
has an AutoClean feature that enables the library to control drive cleaning. (Host controlled drive
cleaning is the default condition.)
Drive cleaning requires cleaning cartridges to be imported into the library. (Note that cleaning
cartridges are imported differently than regular tape cartridges.) A total of three cleaning cartridges
can be imported. These cartridges are stored in fixed slots located at the top of columns 2, 4, and
5. These slots are not counted as part of the slot capacity of the library, are not included in the report
of storage elements, and are not addressable to SCSI hosts.
Working with AutoClean
AutoClean allows the library to clean a drive without instruction from a host.
As AutoClean does not require host intervention, it should only be enabled if the host application
does not or is not configured to control drive cleaning. The cleaning operation is transparent to the
host application and will only occur when a drive requests to be cleaned. The host application will
get a delayed response until the cleaning operation is complete.
AutoClean requires at least one cleaning cartridge and a communication interface to the drive with
the ability of the drive to indicate that cleaning is needed. If AutoClean is enabled, the cleaning slots
will be inventoried by touch.
Enabling/Disabling AutoClean
Use AutoClean to enable or disable the AutoClean feature. (Disabling AutoClean will stop all
cleaning inquiries to the drive.) Be sure to import cleaning cartridges into your library before
enabling AutoClean.
Path: Main menu > More > Setup > Library > AutoClean
To enable/disable autoclean
1. From the Main menu, select More. Select Setup and then select Library. Select AutoClean.
NOTE:
A DLT cleaning tape cannot be used in an SDLT drive.
NOTE:
If the Mailbox is configured as storage, the AutoClean function cannot be
enabled.