ATL P1000 Series Library Unpacking Instructions
Document 6221100-02, Ver. 2, Rel. 0
March 1999
Selecting an Installation Location 7
Power Inlet
4
The power inlet is an IEC-320 connector (see figure 5). For
international applications, replace the power cord with a harmonized
3x1.0 mm
2
power cord approved by the country where used.
Figure 5 AC Power
Receptacle
Rack Current Rating Consideration
5
Consider the current rating of the rack before installing more than one
P1000 library. The P1000 library is rated 6A/3A (120V/230V). This
means that no more than two libraries can be installed in a typical
15A/120V rack.
If other equipment is installed in the rack, determine the total current
rating of all the equipment before adding the P1000 library to the rack.
Grounding
5
The P1000 must be connected to a grounded power outlet. If the
library is rack-mounted, the rack must also be grounded.
Temperature
5
The rack temperature should be less than 90qF (32qC).
Environmental
Requirements
5
The installation site (stand-alone library) or the interior of the rack
(rack-mount library) must meet the following environmental
requirements:
‡ humidity: 20% to 80%, non-condensing
‡ temperature: 59qF to 90qF (15qC to 32qC)
‡ altitude: sea level to 10,000 feet (3,033 meters)
NeutralLine
Ground
~100V to 120V / ~200V to 240V
6A/3A 50Hz/60Hz
IEC-320 Type